RC Details of Walls
Walls
SCOPE:
Core Walls
Shear Walls
DETAILING STANDARDS:
Nominal Cover to Reinforcement:
Internal : 15mm + Δcdev (5 or 10mm)
External : 35mm + Δcdev (5 or 10mm)
Spacing and Size of bars:
Minimum spacing : 75mm (at laps)
Maximum spacing : 400mm
Minimum bar size : 12mm (8mm for Horizontal)
Spacing and Size of Links:
Maximum spacing vertically : 16 x Vertical bar Ø or 2 x Wall thick, whichever is least
Maximum spacing horizontally : 2 x Wall thick
Minimum bar size : 8mm
Bar arrangements:
Typical Arrangement of Links in Wall (If Asc > 0.02Ac):
Typical Wall Details:
Slab / Beam Starters From Wall:
Starters for half landing level slab and beam to be detailed along with wall drg as shown.
Pull-out bars (Kwikastrip or similar approved) to be replaced with couplers if Ø > 16mm and extent
of starters < 2 x lap length or 1.2m.
These details can be used for floor slab and beams as well if the method of construction is slip form
or jump form.
Opening Trimming Detail:
Where,
Superscript as B means British code
Superscript as E means EC2
T L is Tension lap
T A is Tension Anchorage
C L is Comparation lap